It is designed for signal switching and control-circuit isolation within motor starter assemblies and general control panels, not for direct motor load switching.
Contact configuration and switching capacity
Four instantaneous NO contacts, no delayed or lagging switching, no make-before-break. Rated operational current at 24 V is 10 A, derating to 6 A at 230 V, 3 A at 400 V, and 1 A at 690 V. The 220 V DC coil draws 3.2 W closing and holding — no power reduction after pick-up, so factor that into DC supply sizing.
Mounting and environmental tolerance
Fastens via screw or snaps onto DIN rail. IP20 on the front, so it belongs inside a cabinet, not exposed to washdown. Shock rated at 10g / 5 ms and 5g / 10 ms.
Isolation and compliance
Contact reliability: one incorrect operation per 100 million switching cycles at 17 V, 1 mA. RoHS compliance date set to July 1, 2006, covering the substance prohibitions. The lifecycle is listed as current production.