Switching capacity and contact duty
The two NO contacts are rated for 10 A at 24 V AC and 230 V AC, 4.7 A at 60 V AC, 3 A at 110 V AC and 400 V AC, 1.2 A at 220 V AC, and 0.5 A at 440 V AC. At 690 V AC the rating is 1 A. These values define the resistive load curve; for inductive or DC loads, derate per the manufacturer's application guidelines. The contactor switches at up to 10,000 operations per hour, with an arcing time of 10 to 15 ms and a DC switching duration of 7 to 13 ms.
The 73 mm depth and 70 mm height fit within the S00 envelope, leaving room for adjacent devices on the same rail.
Coil and environmental ratings
The DC magnet coil draws 4 W closing power and 4 W holding power. The device is rated for degree of pollution 3 and relative humidity minimum 10 %. Substance prohibitance date is 10/01/2009, indicating RoHS compliance from that date.