Skip to main content
Siemens 3VA1216-5MH32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1216-5MH32-0AH0 SENTRON MCCB, 160 A, 3-Pole, Star

MPN3VA1216-5MH32-0AH0

Siemens SENTRON 3VA1216-5MH32-0AH0, molded case circuit breaker, 3-pole starter protection, 160 A rated continuous current, TM120M thermal-magnetic release, breaking capacity 187 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1216-5MH32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1216-5MH32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C153.6 A
Current at 60 °C150.4 A
Current at 65 °C147.2 A
Current at 70 °C144 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V30 kA
Breaking capacity at 690 V17 kA
3VA1216-5MH32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
3VA1216-5MH32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1216-5MH32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1216-5MH32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1216-5MH32-0AH0 — Mechanical
ParameterValue
Height158 mm
Width105 mm
Depth70 mm

Product details

The Siemens 3VA1216-5MH32-0AH0 is a SENTRON-branded molded case circuit breaker (MCCB) configured for starter protection — meaning it's designed to sit ahead of a motor starter or contactor, providing both short-circuit and overload protection in a single 3-pole device. Its 160 A rated continuous current (Iu) covers moderate motor loads, and the TM120M thermal-magnetic release handles the inverse-time overload curve plus magnetic trip for fault currents. Breaking capacity runs 187 kA at 240 V, 121 kA at 415 V, 30 kA at 440 V, and 17 kA at 690 V — so it handles high available fault current at lower voltages where most industrial panels sit.

Full 160 A rating holds through 50 °C ambient; above that it derates to 153.6 A at 55 °C, 150.4 A at 60 °C, 147.2 A at 65 °C, and 144 A at 70 °C. Dimensions are 158 mm high, 105 mm wide, 70 mm deep, which fits standard SENTRON 3VA panel cutouts; the IP40 front protection is typical for enclosed distribution boards but not for washdown environments.

Frequently asked questions

What does the TM120M release mean on this MCCB?

TM120M is a thermal-magnetic release — the thermal element provides inverse-time overload protection, and the magnetic element provides instantaneous short-circuit trip. The 120M designation indicates the magnetic trip threshold is fixed at 120 % of the rated current.

MPN