Skip to main content
Siemens 3VA1450-6GF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1450-6GF42-0AA0 SENTRON MCCB, 500 A, 4-Pole, 220

MPN3VA1450-6GF42-0AA0
Active

Siemens SENTRON 3VA1450-6GF42-0AA0, molded case circuit breaker, 4-pole, 500 A, breaking capacity 220 kA at 240 V AC, TM240 overcurrent release, line protection, IP40 front, 110 x 184 x 248 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1450-6GF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1450-6GF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C500 A
Current at 45 °C500 A
Current at 50 °C500 A
Current at 55 °C488 A
Current at 60 °C476 A
Current at 65 °C464 A
Current at 70 °C452 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V154 kA
Breaking capacity at 500 V121 kA
Breaking capacity at 690 V17 kA
Power loss, max.122.7 W
3VA1450-6GF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1450-6GF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1450-6GF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1450-6GF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1450-6GF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height248 mm
Width184 mm
Depth110 mm
Height (in)9.76 in
Width (in)7.24 in
Depth (in)4.33 in

Product details

What this 500 A MCCB delivers

The Siemens 3VA1450-6GF42-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 500 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release. The 220 kA interrupting rating at 240 V AC means it can clear a bolted fault at that level without the arc flashing upstream; at 415 V and 440 V it still holds 154 kA, and at 690 V it drops to 17 kA.

Derating and thermal reality

At 55 °C it derates to 488 A, at 60 °C to 476 A, at 65 °C to 464 A, and at 70 °C to 452 A. Maximum power loss is 122.7 W — that heat has to leave the enclosure, so factor it into your panel thermal calculation.

Dimensions: 184 mm wide, 248 mm tall, 110 mm deep. Four-pole frame, so it occupies the full width of a standard MCC bucket or a 600 mm wide enclosure section. Rated insulation voltage 800 V. Mounts with the standard SENTRON screw-clamp kit — verify the bus-bar adapter if you're feeding from a common bus.

Frequently asked questions

Where can I buy 3VA1450-6GF42-0AA0 and what is the lead time?

Sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time commitment.

What is the closest functional second-source to 3VA1450-6GF42-0AA0?

The peer MPNs 5SQ2670-2YA63, 5SQ2670-2YA16, and 5SQ2670-0KA15 are listed as alternates. Verify the interrupting rating and release type against your coordination study before substituting — the 3VA1450 carries 220 kA at 240 V and 154 kA at 415 V, which may exceed the peer's SCCR.

What is the depth of 3VA1450-6GF42-0AA0?

110 mm (4.33 in). Combined with the 184 mm width and 248 mm height, it fits a standard 600 mm deep enclosure with room for rear bus bars.

Will 3VA1450-6GF42-0AA0 drop into a panel specified around 5SQ2670-2YA63 without rewiring?

The 3VA1450 is a 4-pole 500 A frame with a TM240 release; the 5SQ2670 peers are also 4-pole but may differ in mounting hole pattern and bus-bar spacing. Physical interchange is not guaranteed without checking the Siemens mounting template — the 184 mm width matches the standard SENTRON footprint, but verify the lug kit and terminal orientation against your existing bus.

What compliance documentation does Siemens provide for 3VA1450-6GF42-0AA0?

As a SENTRON MCCB, it carries CE marking for the European market and is designed to meet IEC 60947-2. RoHS and REACH declarations are standard from Siemens for this series. UL/CSA listing depends on the specific variant — confirm with the manufacturer's declaration for your region.

MPN
3VA1450-6GF42-0AA0