What this 500 A MCCB delivers
The Siemens 3VA1450-6GF42-0AA0 is a 4-pole SENTRON molded case circuit breaker rated for 500 A continuous at 40 °C, with a TM240 thermal-magnetic overcurrent release. The 220 kA interrupting rating at 240 V AC means it can clear a bolted fault at that level without the arc flashing upstream; at 415 V and 440 V it still holds 154 kA, and at 690 V it drops to 17 kA.
Derating and thermal reality
At 55 °C it derates to 488 A, at 60 °C to 476 A, at 65 °C to 464 A, and at 70 °C to 452 A. Maximum power loss is 122.7 W — that heat has to leave the enclosure, so factor it into your panel thermal calculation.
Dimensions: 184 mm wide, 248 mm tall, 110 mm deep. Four-pole frame, so it occupies the full width of a standard MCC bucket or a 600 mm wide enclosure section. Rated insulation voltage 800 V. Mounts with the standard SENTRON screw-clamp kit — verify the bus-bar adapter if you're feeding from a common bus.