Skip to main content
Siemens 3VA2125-5HK46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2125-5HK46-0AA0 SENTRON MCCB, 25 A, 4-Pole, ETU34

MPN3VA2125-5HK46-0AA0
Active

Siemens SENTRON 3VA2125-5HK46-0AA0, molded case circuit breaker, 4-pole, 25 A, ETU340 electronic trip unit, 187 kA at 240 V, 121 kA at 415 V, IP40 front.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2125-5HK46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2125-5HK46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C25 A
Current at 45 °C25 A
Current at 50 °C25 A
Current at 55 °C25 A
Current at 60 °C25 A
Current at 65 °C25 A
Current at 70 °C25 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 500 V76 kA
Breaking capacity at 690 V17 kA
Power loss, max.0.6 W
3VA2125-5HK46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU340
3VA2125-5HK46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2125-5HK46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2125-5HK46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2125-5HK46-0AA0 — Mechanical
ParameterValue
Height181 mm
Width140 mm
Depth86 mm
Height (in)7.1 in
Width (in)5.5 in
Depth (in)3.4 in

Product details

What this MCCB delivers

The Siemens SENTRON 3VA2125-5HK46-0AA0 is a 4-pole molded case circuit breaker (MCCB) rated for 25 A continuous current across the full ambient range from 40 °C to 70 °C — no derating needed up to that ceiling. It carries an ETU340 electronic trip unit, which gives you adjustable long-time, short-time, instantaneous, and ground-fault protection curves. The interrupting ratings are substantial: 187 kA at 240 V AC, 121 kA at 415 V and 440 V, 76 kA at 500 V, and 17 kA at 690 V. That puts it in the high-interrupting-capacity class for industrial distribution panels where fault currents can be severe.

The ETU340 release lets you coordinate selectively with downstream breakers: you can set the short-time pickup and delay so a feeder fault clears before this main trips, keeping the rest of the bus live.

It's designed for panel mounting with screw connections — no DIN-rail clip on this frame size. The 4-pole configuration covers three-phase plus neutral, with the neutral protection adjustable to OFF or 100% of the phase setting.

Frequently asked questions

What is the interrupting rating of 3VA2125-5HK46-0AA0 at 415 V?

121 kA at 415 V AC, and the same 121 kA at 440 V. At 240 V it's 187 kA, at 500 V it's 76 kA, and at 690 V it's 17 kA.

What trip unit does this MCCB use?

It uses the ETU340 electronic trip unit, which provides adjustable long-time, short-time, instantaneous, and ground-fault protection curves.

Where can I buy 3VA2125-5HK46-0AA0 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no online stock or price is listed here.

Will 3VA2125-5HK46-0AA0 drop into a panel specified for 3VA2125-8KQ42-0AA0?

Both are 4-pole 25 A SENTRON 3VA frame-size breakers, so the mounting footprint and bus-bar spacing are the same. The difference is in the trip unit and accessories — the 5HK46 variant carries the ETU340 release, while the 8KQ42 variant uses a different release. Verify the trip curve and auxiliary contact configuration against your coordination study before swapping.

MPN
3VA2125-5HK46-0AA0