Skip to main content
Siemens 3VA2163-8HN36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA2163-8HN36-0AA0 SENTRON MCCB, 63 A, 3-Pole, ETU35

MPN3VA2163-8HN36-0AA0
Active

Siemens SENTRON 3VA2163-8HN36-0AA0, Molded case circuit breaker, 3-pole, 63 A, ETU350 electronic trip unit, Line protection, 440 kA at 240 V, 330 kA at 415 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA2163-8HN36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA2163-8HN36-0AA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C63 A
Current at 60 °C63 A
Current at 65 °C63 A
Current at 70 °C63 A
Switching capacity classL
Breaking capacity at 240 V440 kA
Breaking capacity at 415 V330 kA
Breaking capacity at 440 V330 kA
Breaking capacity at 500 V220 kA
Breaking capacity at 690 V53 kA
Power loss, max.3.1 W
3VA2163-8HN36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeETU350
3VA2163-8HN36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA2163-8HN36-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA2163-8HN36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-40 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA2163-8HN36-0AA0 — Mechanical
ParameterValue
Height181 mm
Width105 mm
Depth86 mm
Height (in)7.1 in
Width (in)4.1 in
Depth (in)3.4 in

Product details

63 A MCCB with ETU350 — interrupting capacity for high-fault panels

The Siemens 3VA2163-8HN36-0AA0 is a SENTRON 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C, with no derating needed at elevated temperatures. The ETU350 electronic trip unit gives adjustable long-time (tr 0.5–17 s) and short-time delay (tsd up to 0.4 s) for selective coordination downstream.

Trip unit and coordination

The ETU350 electronic release provides LSI protection: long-time (tr), short-time (tsd with I²t on/off), and instantaneous. Adjustable tr from 0.5 to 17 seconds lets you ride through motor inrush without nuisance trips. Short-time delay adjustable up to 0.4 s enables zone-selective interlocking with downstream breakers. Power loss is 3.1 W maximum, negligible for panel thermal budgeting.

Frequently asked questions

Where can I buy 3VA2163-8HN36-0AA0 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit the order code and quantity for a firm delivery commitment.

Will 3VA2163-8HN36-0AA0 drop into a panel specified for 3VA2163-8HM32-0AA0 without rewiring?

Both are 3-pole 63 A SENTRON MCCBs in the same 3VA2 frame size (105 mm wide, 181 mm tall, 86 mm deep), so the physical footprint and wiring space are identical. The difference is the trip unit: the -8HN36-0AA0 carries the ETU350 electronic release, while the -8HM32-0AA0 uses a different release variant. No rewiring needed for the same bus and lug arrangement, but verify the trip curve settings match your coordination study.

What is the interrupting capacity of this MCCB at 415 V?

330 kA at 415 V, and the same 330 kA at 440 V. At 690 V it drops to 53 kA. The 440 kA rating at 240 V covers low-voltage high-fault applications like transformer secondaries.

MPN
3VA2163-8HN36-0AA0