63 A MCCB with ETU350 — interrupting capacity for high-fault panels
The Siemens 3VA2163-8HN36-0AA0 is a SENTRON 3-pole molded case circuit breaker rated for 63 A continuous current across the full ambient range from 40 °C to 70 °C, with no derating needed at elevated temperatures. The ETU350 electronic trip unit gives adjustable long-time (tr 0.5–17 s) and short-time delay (tsd up to 0.4 s) for selective coordination downstream.
Trip unit and coordination
The ETU350 electronic release provides LSI protection: long-time (tr), short-time (tsd with I²t on/off), and instantaneous. Adjustable tr from 0.5 to 17 seconds lets you ride through motor inrush without nuisance trips. Short-time delay adjustable up to 0.4 s enables zone-selective interlocking with downstream breakers. Power loss is 3.1 W maximum, negligible for panel thermal budgeting.