Skip to main content
Siemens 3VA4110-1BB24-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA4110-1BB24-0AA0 SENTRON MCCB, 100 A, 2-Pole

MPN3VA4110-1BB24-0AA0
Active

Siemens SENTRON 3VA4110-1BB24-0AA0, molded-case circuit breaker, 2-pole, 100 A at 40 °C, 415 V AC, IP40 front, UL HEAB.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA4110-1BB24-0AA0 — Identification
ParameterValue
Product designationMolded-case circuit breaker
Brand / rangeSENTRON
Product versionmolded case switch
3VA4110-1BB24-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C100 A
Current at 60 °C100 A
Current at 65 °C97 A
Current at 70 °C94 A
Power loss, max.12.3 W
3VA4110-1BB24-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeMCS110
Overcurrent protection functionI
Ground-fault monitoringWithout
3VA4110-1BB24-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeInfeed side: Low tab
Protection class (IP), frontIP40
3VA4110-1BB24-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA4110-1BB24-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA4110-1BB24-0AA0 — Mechanical
ParameterValue
Height129.4 mm
Width50.8 mm
Depth75.1 mm
Height (in)5.09 in
Width (in)2 in
Depth (in)2.96 in

Product details

100 A, 2-pole MCCB — flat thermal curve to 60 °C

The Siemens SENTRON 3VA4110-1BB24-0AA0 is a 2-pole molded-case circuit breaker rated 100 A at 40 °C, with the same 100 A hold at 45 °C, 50 °C, 55 °C, and 60 °C — no derating needed across that band. That flat curve means a panel running at 60 °C ambient still gets full 100 A capacity, which simplifies thermal budgeting in a crowded enclosure.

MCS110 overcurrent release — fixed I²t, no trip indicator

The overcurrent release is the MCS110, a fixed thermal-magnetic design with no adjustable I²t curve. The trip indicator is absent, so fault diagnosis relies on the breaker position or an external auxiliary contact — none are included (0 CO contacts for auxiliary contacts). The protection function is I (instantaneous only, no ground-fault or undervoltage release). For DC network applications, Siemens directs to the 3VA device manual.

The breaker measures 75.1 mm deep, 50.8 mm wide, and 129.4 mm high — a 2-inch wide body that fits a standard DIN-rail or panel-mount cutout. Front protection is IP40, meaning tools or fingers won't contact live parts from the front, but the sides and back are not sealed against dust ingress. Maximum power loss is 12.3 W, which should be factored into enclosure ventilation if several breakers are ganged.

Current lifecycle — no EOL notice

No successor MPN is listed in the evidence. For BOM planning, the part remains in active catalog status; any future PCN would be managed through the standard Siemens obsolescence process.

MPN