Skip to main content
Siemens 3VM1450-5EE42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1450-5EE42-0AA0 Circuit Breaker, 500A, 55kA @ 415

MPN3VM1450-5EE42-0AA0
Active

Siemens 3VM1 IEC frame 630, 4-pole circuit breaker, 500 A, breaking capacity class S, Icu = 55 kA at 415 V, TM220 line protection, ATFM, overload Ir = 350…500 A, short-circuit Ii = 10 x In, N conductor unprotected, nut keeper kit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VM1450-5EE42-0AA0 — Specifications
ParameterValue
Group codeP360
Product group5377
Product classC: products manufactured / produced to order, which cannot be reused or re-utilized or be returned against credit.
SeriesOrdering Data Overview
Export control regulationsAL : N / ECCN : 9N9999
Compliance with the substance restrictions according to RoHS directiveSince: 01-06-12

Product details

The 3VM1450-5EE42-0AA0 is a 4-pole IEC frame 630 circuit breaker rated 500 A continuous, with a 55 kA interrupting capacity at 415 V AC (breaking capacity class S). The TM220 thermal-magnetic trip unit provides adjustable overload protection (Ir = 350…500 A) and fixed instantaneous short-circuit protection at 10× In. The N conductor is unprotected — meaning the neutral pole is a solid link, not a switched or protected pole. This is standard for 3-phase, 4-wire systems where neutral overcurrent protection is not required by local code (e.g., solidly-grounded wye systems). The nut keeper kit simplifies panel assembly: the breaker ships with captive hardware that prevents nuts from dropping into live buswork during installation.

The 3VM1 frame is a fixed-mount, DIN-rail-compatible circuit breaker. The packaging dimensions (261 × 208 × 170 mm) give a rough envelope for panel layout — allow clearance for the nut keeper kit and cable entry. The 4-pole configuration occupies four module widths on the DIN rail; verify that the panel's gland plate and fill factor accommodate the 500 A cable terminations (typically 2× 185 mm² or 1× 300 mm² per phase, depending on derating).

Frequently asked questions

What is the interrupting capacity of this breaker?

The breaking capacity class S provides Icu = 55 kA at 415 V AC. This is the maximum fault current the breaker can safely interrupt under standard IEC test conditions.

Where can I buy the 3VM1450-5EE42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or lead-time figures are published here.

MPN
3VM1450-5EE42-0AA0