Skip to main content
Siemens 5SP3450-3 — 4-Pole MCB (DIN Rail)

Siemens 5SP3450-3 SENTRON MCB, 4P, 50A, 25kA, Char E

MPN5SP3450-3
Active

Siemens SENTRON 5SP3450-3, 4-pole miniature circuit breaker, 50 A rated at 400 V AC, 25 kA breaking capacity (EN 60898), characteristic E, 6 MW, standard rail mount, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SP3450-3 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SP3450-3 — Ratings
ParameterValue
Number of poles4
Rated current (In), AC50 A
Rated frequency25 kA
5SP3450-3 — Protection
ParameterValue
Tripping characteristic (trip curve)E
Rated breaking capacity (Icn), per EN 6089825 kA
Overvoltage categoryIV
Pollution degree3
Degree of protection (IP)IP40, with connected conductors
5SP3450-3 — Mechanical
ParameterValue
Width in modular units6
Height128 mm
Depth76.3 mm
Fastening / mounting methodstandard rail
Tightening torque, max.70 °C
Tightening torque, min.-40 °C
SealableYes
5SP3450-3 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)20 000

Product details

Characteristic E is the tripping curve here — it's a delayed thermal-magnetic release designed for circuits with moderate inrush, like groups of fluorescent lighting or small transformers.

At 40 °C it derates to 47.5 A, at 50 °C to 45 A.

Snap-on standard rail (DIN rail) mounting. 6 modular width units (MW) wide — that's about 108 mm on the rail. The 128 mm height and 76.3 mm depth fit a standard distribution board depth; the depth figure is the body only, not including the handle throw or conductor bend radius. Terminals accept solid or stranded copper from 2.5 mm² up to 50 mm² — covers the range from a 6 mm² subfeed to the 35 mm² or 50 mm² main feeder. Saddle terminals and box-terminal infeed are both present; the locking device (integrated slide, lockable with a padlock, wire seal, or cable tie) is useful for utility-metering or safety-disconnect applications where unauthorized operation must be prevented. Sealable, per the evidence — the enclosure can be sealed to prevent tampering, which is often a requirement for revenue-metering or landlord sub-metering installations.

Shock resistance is rated at 30 g for at least 3 impacts of 11 ms duration — that's the mechanical robustness for transport and seismic events, not a continuous vibration spec. For applications with sustained vibration (near a large motor or compressor), you'd want additional dampening or a different mounting method.

Frequently asked questions

Where can I buy 5SP3450-3 and how do I get a price?

The 5SP3450-3 is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SP3450-3?

The rated breaking capacity is 25 kA per EN 60898 at 400 V AC. This is the maximum fault current it can safely interrupt.

What conductor sizes does the 5SP3450-3 accept?

Solid conductors from 2.5 mm² to 50 mm², and stranded conductors from 2.5 mm² to 50 mm². Saddle terminals are provided.

What is the temperature derating for 5SP3450-3?

Rated 50 A at 30 °C. Derates to 47.5 A at 40 °C, 46.25 A at 45 °C, 45 A at 50 °C, and 43.75 A at 55 °C. Size your continuous load against the ambient temperature in the enclosure.

MPN