At 16 A it handles a 3.5 kW resistive load on 230 V single-phase per pole. The 10 kA IEC 60898-1 rating is the domestic breaker standard; the 20 kA IEC 60947-2 rating means it can also sit in an industrial distribution board with higher prospective fault current without derating.
Sealable for lockout/tagout. Operating temperature range -40 to 75 °C, with a derating curve above 35 °C (15.23 A at 40 °C, 14 A at 55 °C).