Specifications
| Parameter | Value |
|---|---|
| Fault type | Broken wire 4...20 mA |
| Type of filter | Single low pass input filter -3 dB 15 Hz +/- 20 % |
| Protection type | Internal fuse |
| Range of product | Modicon Quantum automation platform |
| Product or component type | Intrinsically safe current input module |
| Bus current requirement | 1500 mA |
| Power dissipation in | 7.5 W |
| Relative humidity | 95 % without condensation |
| Operating altitude | <= 16404.2 ft (5000 m) |
| Standards | Directive ATEX 94/9/EC EN 50039 CSA C22.2 No 142 EN 50014 EN 50020 EN 50284 EN 50281-1-1 UL 508 |
| Marking | CE II1 G/D-EEx ia IIC |
| Category | 18155-QUANTUM I/O & POWER SUPPLIES |
All specifications+20 ▾
| Parameter | Value |
|---|---|
| Dust zone | Outside zone |
| Update time | 750 ms |
| Module format | Standard |
| Input impedance | 100 Ohm +/- 0.1 % |
| Linearity error | 0.003 % of full scale |
| Product destination | In conjunction with products for zone 20, 21 or 22 |
| Analogue input range | 0...20 mA 0...25 mA 4...20 mA |
| Software designation | Concept V2.2 and above ProWORX Unity Pro |
| Analogue input number | 8 |
| Common mode rejection | > 100 dB 50/60 Hz |
| Hot swapping fallback | Not allowed per intrinsic safety standards |
| Absolute maximum input | 25 mA internally limited |
| Absolute accuracy error | +/- 0.05 % typical of full scale 77 °F (25 °C) +/- 0.1 % of full scale maximum 77 °F (25 °C) |
| Analogue input resolution | 0...16000 counts 4...20 mA 0...20000 counts 0...20 mA 0...25000 counts 0...25 mA 0...4095 counts 4...20 mA |
| Isolation between channels and bus | 2500 V for 1 minute DC 1780 V 47...63 Hz AC |
| Ambient air temperature for storage | -40...185 °F (-40...85 °C) |
| Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3 |
| Ambient air temperature for operation | 32...140 °F (0...60 °C) |
| Resistance to electrostatic discharge | 4 kV contact IEC 801-2 8 kV on air IEC 801-2 |
| Accuracy drift according to temperature | +/- 0.0025 % typical of full scale/°C 0.005 % maximum of full scale/°C |