Skip to main content
Schneider Electric 140AII33010 — Digital Input Modules

Schneider Electric 140AII33010 Quantum Intrinsically Safe

MPN140AII33010
Obsolete

Schneider Electric Modicon Quantum 140AII33010 intrinsically safe current input module, 8 analogue inputs, 4-20 mA / 0-20 mA / 0-25 mA, ATEX II 1 G/D EEx ia IIC, standard module format.

$2,857.50Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

140AII33010 key specifications
ParameterValue
Fault typeBroken wire 4...20 mA
Type of filterSingle low pass input filter -3 dB 15 Hz +/- 20 %
Protection typeInternal fuse
Range of productModicon Quantum automation platform
Product or component typeIntrinsically safe current input module
Bus current requirement1500 mA
Power dissipation in7.5 W
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)
StandardsDirective ATEX 94/9/EC EN 50039 CSA C22.2 No 142 EN 50014 EN 50020 EN 50284 EN 50281-1-1 UL 508
MarkingCE II1 G/D-EEx ia IIC
Category18155-QUANTUM I/O & POWER SUPPLIES

All specifications

140AII33010 additional specifications
ParameterValue
Dust zoneOutside zone
Update time750 ms
Module formatStandard
Input impedance100 Ohm +/- 0.1 %
Linearity error0.003 % of full scale
Product destinationIn conjunction with products for zone 20, 21 or 22
Analogue input range0...20 mA 0...25 mA 4...20 mA
Software designationConcept V2.2 and above ProWORX Unity Pro
Analogue input number8
Common mode rejection> 100 dB 50/60 Hz
Hot swapping fallbackNot allowed per intrinsic safety standards
Absolute maximum input25 mA internally limited
Absolute accuracy error+/- 0.05 % typical of full scale 77 °F (25 °C) +/- 0.1 % of full scale maximum 77 °F (25 °C)
Analogue input resolution0...16000 counts 4...20 mA 0...20000 counts 0...20 mA 0...25000 counts 0...25 mA 0...4095 counts 4...20 mA
Isolation between channels and bus2500 V for 1 minute DC 1780 V 47...63 Hz AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2
Accuracy drift according to temperature+/- 0.0025 % typical of full scale/°C 0.005 % maximum of full scale/°C

Product details

Intrinsically safe current input for hazardous dust zones

The 140AII33010 is an 8-channel intrinsically safe current input module for the Modicon Quantum automation platform, designed to interface with field transmitters in explosive atmospheres classified as zone 20, 21, or 22 (dust). Its ATEX marking CE II1 G/D-EEx ia IIC certifies it for use in gas and dust hazardous areas with intrinsically safe circuits, meeting Directive ATEX 94/9/EC, EN 50014, EN 50020, EN 50284, and EN 50281-1-1.

Input ranges, diagnostics, and signal conditioning

Each of the 8 channels accepts standard process current loops: 0-20 mA, 4-20 mA, or 0-25 mA, with a 100 Ohm input impedance and an internal fuse for overcurrent protection. Resolution spans 0-16000 counts (4-20 mA), 0-20000 counts (0-20 mA), or 0-25000 counts (0-25 mA), with a linearity error of 0.003% of full scale and typical absolute accuracy of ±0.05% at 25 °C.

Isolation, power budget, and thermal load

Channel-to-bus isolation is rated 2500 V DC for 1 minute and 1780 V AC at 47-63 Hz, providing galvanic separation between the intrinsically safe field circuits and the Quantum backplane. The module draws 1500 mA from the 5 V bus and dissipates 7.5 W — a significant load that must be factored into the rack's power budget and the enclosure's thermal management.

Obsolete — sourcing via independent channels

The module is available through independent surplus and broker channels. Software support includes Concept V2.2 and above, ProWORX, and Unity Pro — existing configurations should migrate without re-engineering if the module is replaced with the same order code.

Frequently asked questions

What is the 140AII33010's ATEX marking and what does it mean?

The marking is CE II1 G/D-EEx ia IIC, certifying the module for intrinsically safe circuits in gas Group IIC and dust zones 20, 21, or 22 per ATEX 94/9/EC.

How many analogue inputs does the 140AII33010 have and what current ranges does it accept?

It has 8 analogue inputs accepting 0-20 mA, 4-20 mA, or 0-25 mA current loops, with a 100 Ohm input impedance and internal fuse protection.

What is the bus current draw and power dissipation of the 140AII33010?

The module draws 1500 mA from the Quantum backplane and dissipates 7.5 W, which must be accounted for in the rack power budget and enclosure cooling.

Can the 140AII33010 be hot-swapped?

No. Hot swapping is not allowed per intrinsic safety standards. The rack must be powered down before replacing the module.

MPN