Skip to main content
Schneider Electric 140AMM09000C

Schneider 140AMM09000C Analog I/O Module

MPN140AMM09000C
End of Life

Analog Input Module

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

140AMM09000C key specifications
ParameterValue
Fault typeOpen circuit input/output circuit Overtacking scale (unipolar) input circuit Status byte output circuit
Type of filterSingle pole low pass - 3 dB at 21 Hz +/- 20 % input circuit
Range of productModicon Quantum automation platform
Analogue input typeBipolar current +/- 20 mA 15 bits DC Bipolar voltage +/- 10 V 16 bits DC Bipolar voltage +/- 5 V 15 bits DC Unipolar current 0...20 mA 15 bits DC Unipolar offset current 4...20 mA 14 bits DC Unipolar offset voltage 1...5 V 14 bits DC Unipolar voltage 0...10 V 16 bits DC Unipolar voltage 0...5 V 15 bits DC
Product or component typeInput/output analog module
Loop voltage0...60 V DC with external resistance output circuit 7...30 V DC output circuit
Maximum voltage drop<30 V DC 20 mA
Bus current requirement350 mA
External power requirement7...30 V output circuit
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)
StandardsUL 508 CSA C22.2 No 142

All specifications

140AMM09000C additional specifications
ParameterValue
Offset+/- 0.0014 % of full scale maximum/°C 0...60 °C input circuit
MarkingCE
Category18155-QUANTUM I/O & POWER SUPPLIES
Linearity2.4 % over and under range voltage 2.4 % over range, and - 9.6 % under range current Monotonic +/- 1 LSB input Monotonic +/- 1 LSB output
Gain shift+/- 0.002 of full scale maximum 0...60 °C input circuit
Update time15 ms output circuit 320 ms input circuit
Setting time900 µs to +/- 0.1 % of the final value output circuit
Module formatStandard
I (O modularity)6 channels
Input impedance> 10 MOhm voltage > 250 Ohm current
Local signalling1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 6 LEDs (green) for channel is turned on 6 LEDs (red) for channel fault
Protective treatmentConformal coating Humiseal 1A33
Analogue input number4
Analogue output range4...20 mA
Common mode rejection> 80 dB 50/60 Hz input circuit
Absolute maximum input+/- 25 mA current +/- 50 V voltage
Addressing requirement2 output words 5 input words
Analogue output number2
Absolute accuracy error+/- 0.004 % of full scale 32...140 °F (0...60 °C) output circuit +/- 0.007 %/°C of full scale maximum 32...140 °F (0...60 °C) output circuit +/- 0.03 % 77 °F (25 °C) input circuit +/- 0.05 % of full scale maximum 77 °F (25 °C) input circuit +/- 0.20 % of full scale 77 °F (25 °C) output circuit
Analogue output resolution12 bits
Isolation between channels500 V AC for 1 minute 750 V DC for 1 minute
Isolation between channels and bus500 V AC for 1 minute 750 V DC for 1 minute
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Isolation between input channel and output channel500 V for 1 minute 750 V for 1 minute
MPN
140AMM09000C