Skip to main content
Schneider Electric 140ATI03000C

Schneider 140ATI03000C Analog Input Module

MPN140ATI03000C
Obsolete

Analog Input Module

$3,780.96 – $5,148.00Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

140ATI03000C key specifications
ParameterValue
Fault typeBroken wire Overtacking scale
Type of filterNotch filter - 3 dB at 50/60 Hz Single pole low pass - 3 dB at 20 Hz
Range of productModicon Quantum automation platform
Analogue input typeThermocouple - 210...760 °C thermocouple J Thermocouple - 270...1000 °C thermocouple E Thermocouple - 270...1370 °C thermocouple K Thermocouple - 270...400 °C thermocouple T Thermocouple - 50...1665 °C thermocouple R Thermocouple - 50...1665 °C thermocouple S
Product or component typeAnalogue input module
Bus current requirement280 mA
Power dissipation in1.5 W
Relative humidity95 % without condensation
Operating altitude<= 16404.2 ft (5000 m)
StandardsUL 508 CSA C22.2 No 142
MarkingCE
CategoryUS1PC2118155

All specifications

140ATI03000C additional specifications
ParameterValue
Update time1000 ms
Module formatStandard
Linearity error1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C 1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C
Local signalling1 LED (green) for bus communication is present (Active) 1 LED (red) for external fault 8 LEDs (green) for channel is turned on 8 LEDs (red) for channel fault
Protective treatmentConformal coating Humiseal 1A33
Analogue input number8
Common mode rejection> - 120 dB 50/60 Hz
Addressing requirement10 input words
Absolute accuracy error+/- 2 °C plus + 0.1 % of reading thermocouple E +/- 2 °C plus + 0.1 % of reading thermocouple J +/- 2 °C plus + 0.1 % of reading thermocouple K +/- 2 °C plus + 0.1 % of reading thermocouple T +/- 4 °C plus + 0.1 % of reading thermocouple R +/- 4 °C plus + 0.1 % of reading thermocouple S
Analogue input resolution16 bits
Cold junction compensationInternal 32...140 °F (0...60 °C)
Isolation between channels300 V DC 220 V AC
Isolation between channels and bus1780 V AC 60 s 2500 V DC 60 s
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Resistance to electromagnetic fields9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient air temperature for operation32...140 °F (0...60 °C)
Resistance to electrostatic discharge4 kV contact IEC 801-2 8 kV on air IEC 801-2
Accuracy drift according to temperature0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
MPN
140ATI03000C