Specifications

18565 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)500 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
18565 — Electrical Ratings
ParameterValue
Rated current (In)125 A
Rated operational voltage (Ue)230...415 V AC 50/60 Hz
Poles description2P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Device location in systemOutgoer Group incomer
Mechanical durability (operating cycles)20000 cycles
18565 — Identification
ParameterValue
Product / component typeAdd-on residual current device
Device short nameVigi C120
18565 — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail
Width in 9 mm modules7
Terminal connectionsTunnel type terminals 1...35 mm² flexible Tunnel type terminals 1.5...50 mm² rigid
Wire stripping length15 mm
Terminal tightening torque3.5 N.m
Width117 mm
Height87 mm
Depth73 mm
18565 — Environmental
ParameterValue
Operating ambient temperature-25...40 °C
Storage ambient temperature-40...70 °C
IP degree of protectionIP20
Pollution degree3 conforming to IEC 60947-2
Relative humidity95 % at 55 °C
Operating altitude2000 m
Tropicalisation2 conforming to EN 61009
18565 — Approvals
ParameterValue
StandardsIEC 60947-2 EN 61009
MPN