Schneider Electric 21553
MPN21553
Obsolete
iDPN - circuit breaker - iDPN N - 1P + N - 2A - C curve
$68.58Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Range of product | Clario |
| Product or component type | Miniature circuit-breaker |
| Voltage | 440 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 4 kVEN/IEC 60947-2 |
| Breaking capacity | 6000 A Icn 230 V AC 50/60 Hz EN 60898-1 10 kA Icu 230 V AC 50/60 Hz EN/IEC 60947-2 |
| Line rated current | 2 A |
| [Ics] rated service breaking capacity | 6000 A 100 % x Icn at 230 V AC 50/60 Hz conforming to EN 60898-1 |
| Network frequency | 50/60 Hz |
| Poles description | 1P + N |
| Number of protected poles | 1 |
All specifications
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | 35 mm symmetrical DIN rail |
| Wire stripping length | 0.5 in (13 mm) |
| Connections - terminals | Tunnel type terminals 0.0005...0.02 in² (0.33...10 mm²) flexible Tunnel type terminals 0.001...0.02 in² (0.75...16 mm²) rigid |
| Relative humidity | 95 % 131 °F (55 °C) |
| Operating altitude | 6561.68 ft (2000 m) |
| Depth | 2.8 in (70 mm) |
| Width | 0.7 in (18 mm) |
| Height | 3.1 in (80 mm) |
| Electrical durability | 20000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN 60898 IEC 60947-2 |
| Range | Clario |
| Category | 01078-DE2 MISC |
| Curve code | C |
| 9 mm pitches | 2 |
| Tropicalisation | 2 IEC 60068-1 |
| Limitation class | 3 EN 60898-1 |
| Local signalling | ON/OFF indication |
| Neutral position | Left |
| Device short name | iDPN N |
| Tightening torque | 17.7 lbf.in (2 N.m) |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 5...10 x In |
| Earth-leakage protection | Separate block |
| Contact position indicator | Yes |
| Ambient air temperature for storage | -40...158 °F (-40...70 °C) |
| Ambient air temperature for operation | -13...158 °F (-25...70 °C) |
MPN