Specifications

24306 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Range of productC60
Product or component typeMiniature circuit-breaker
[Ue] rated operational voltage230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz 230/400 V AC 50/60 Hz 130 V AC 50/60 Hz per pole
Breaking capacity20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 3 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 15 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2
Current2 A at 30 °C
[Ics] rated service breaking capacity15 kA conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz 7.5 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz 6000 A conforming to EN 60898 - 230/400 V AC 50/60 Hz 2.25 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description1P
Number of protected poles1
Mounting modeClip-on

All specifications

24306 additional specifications
ParameterValue
Mounting support35 mm symmetrical DIN rail
Connections - terminalsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Relative humidity95 % at 55 °C
Operating altitude2000 m
Depth73 mm
Width18 mm
Height81 mm
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN 60898
RangeMulti9
Curve codeC
9 mm pitches2
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60947-2
Local signallingON/OFF indication
Device short nameC60N
Tightening torquePower circuit: 2 N.m upside 2 N.m downside
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-25...60 °C
Comb busbar and distribution block compatibilityNO
MPN
24306