Skip to main content
Schneider Electric 25111

Schneider Electric 25111

MPN25111
Obsolete

C60 - circuit breaker - C60H - 2P - 2A - D curve

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

25111 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Range of productC60
Product or component typeMiniature circuit-breaker
[Ue] rated operational voltage440 V AC 50/60 Hz 230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz 230/400 V AC 50/60 Hz
Breaking capacity10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 25 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2 30 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 40 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2 50 kA Icu at <= 250 V DC 4P conforming to EN/IEC 60947-2
Current2 A at 40 °C
[Ics] rated service breaking capacity7.5 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz 7500 A conforming to EN 60898 - 230/400 V AC 50/60 Hz 15 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz 5 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description2P
Number of protected poles2
Mounting modeClip-on

All specifications

25111 additional specifications
ParameterValue
Mounting support35 mm symmetrical DIN rail
Connections - terminalsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Relative humidity95 % at 55 °C
Operating altitude2000 m
Depth73 mm
Width36 mm
Height81 mm
Mechanical durability20000 cycles
StandardsEN 60898 EN/IEC 60947-2
RangeMulti9
Curve codeD
9 mm pitches4
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60947-2
Local signallingON/OFF indication
Device short nameC60H
Tightening torquePower circuit: 2 N.m upside 2 N.m downside
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit10...14 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-25...60 °C
Comb busbar and distribution block compatibilityNO
MPN
25111