C60 - circuit breaker - C60L - 4P - 10A - C curve

$135.38Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

25449 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Range of productC60
Product or component typeMiniature circuit-breaker
[Ue] rated operational voltage440 V AC 50/60 Hz 230...240 V AC 50/60 Hz 400...415 V AC 50/60 Hz <= 250 V DC
Breaking capacity20 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 125 V DC 2P conforming to EN/IEC 60947-2 50 kA Icu at 125 V DC 3P conforming to EN/IEC 60947-2 60 kA Icu at <= 250 V DC 4P conforming to EN/IEC 60947-2
Current10 A at 40 °C
[Ics] rated service breaking capacity10 kA conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 25 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz 12.5 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description4P
Number of protected poles4
Mounting modeClip-on

All specifications

25449 additional specifications
ParameterValue
Mounting support35 mm symmetrical DIN rail
Connections - terminalsTunnel type terminals16 mm² flexible Tunnel type terminals25 mm² rigid
Relative humidity95 % at 55 °C
Operating altitude2000 m
Depth73 mm
Width72 mm
Height81 mm
Mechanical durability20000 cycles
StandardsEN/IEC 60947-2 EN 60898
RangeMulti9
Curve codeC
9 mm pitches8
Tropicalisation2 conforming to IEC 60068-1
Limitation class3 conforming to EN/IEC 60947-2
Local signallingON/OFF indication
Device short nameC60L
Tightening torquePower circuit: 2 N.m upside 2 N.m downside
Device applicationDistribution
Trip unit technologyThermal-magnetic
Magnetic tripping limit7...10 x In
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to IEC 60947-2
Contact position indicatorYes
Ambient air temperature for storage-40...70 °C
Ambient air temperature for operation-25...60 °C
Comb busbar and distribution block compatibilityNO
MPN