circuit breaker Compact NS100N - TMD - 25 A - 4 poles 4d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

29654 key specifications
ParameterValue
Control typeToggle
Network typeAC DC
Protection typeShort-circuit protection (magnetic) Overload protection (thermal) Protection of the fourth pole
Range of productCompact NS100...630
Product or component typeCircuit breaker
Long time pick-up adjustment type irAdjustable
Instantaneous pick-up adjustment type iiFixed
Voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2 750 V DC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity85 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 600 V AC 50/60 Hz conforming to UL 508 25 kA at 480 V AC 50/60 Hz conforming to UL 508 35 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 8 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC 85 kA at 240 V AC 50/60 Hz conforming to UL 508 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Current100 A at 40 °C 100 A at 65 °C

All specifications

29654 additional specifications
ParameterValue
Breaking capacity codeN
[Ics] rated service breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 4 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description4P
Protected poles description4t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60947
Depth86 mm
Width140 mm
Height161 mm
Electrical durability30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability50000 cycles
StandardsIEC 60947-2
Trip unit nameTM-D
Local signallingPositive contact indication
Neutral positionLeft
Trip unit rating25 A at 40 °C
Device short nameCompact NS100N
Device applicationDistribution
Circuit breaker nameCompact NS100N
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-2
Neutral protection setting1 x Ir
Long time pick-up adjustment range0.8...1 x In
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
Instantaneous pick-up adjustment range300 A