Skip to main content
Schneider Electric 29670

Schneider Electric 29670

MPN29670
Obsolete

circuit breaker Compact NS100H - TMD - 100 A - 3 poles 3d

$178.74Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

29670 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Protection typeShort-circuit protection (magnetic) Overload protection (thermal)
Range of productCompact NS100...630
Product or component typeCircuit breaker
Long time pick-up adjustment type irAdjustable
Instantaneous pick-up adjustment type iiFixed
Voltage750 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2 750 V DC conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 35 kA at 600 V AC 50/60 Hz conforming to NEMA AB1 HIC 65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 600 V AC 50/60 Hz conforming to UL 508 85 kA at 240 V AC 50/60 Hz conforming to UL 508 65 kA at 480 V AC 50/60 Hz conforming to UL 508 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Current100 A at 40 °C 100 A at 65 °C

All specifications

29670 additional specifications
ParameterValue
Breaking capacity codeH
[Ics] rated service breaking capacity65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 17.5 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
Network frequency50/60 Hz
Poles description3P
Protected poles description3t
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate
Connection pitch35 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60947
Depth86 mm
Width105 mm
Height161 mm
Electrical durability30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability50000 cycles
StandardsIEC 60947-2
Trip unit nameTM-D
Local signallingPositive contact indication
Trip unit rating100 A
Device short nameCompact NS100H
Device applicationDistribution
Circuit breaker nameCompact NS100H
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60947-2
Long time pick-up adjustment range0.8...1 x In
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
Instantaneous pick-up adjustment range800 A
MPN
29670