Skip to main content
Schneider Electric 32715 — Molded Case Circuit Breakers (MCCB)

Schneider Electric 32715

MPN32715
Obsolete

circuit breaker Compact NS400H - STR53UE - 250 A - 3 poles 3d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

32715 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
32715 — Mechanical
ParameterValue
Height255 mm
Width140 mm
Depth110 mm
32715 — Electrical
ParameterValue
[In] rated current400 A at 40 °C 320 A at 65 °C
Breaking capacity100 kA at 240 V AC 50/60 Hz conforming to NEMA AB1 HIC 65 kA at 480 V AC 50/60 Hz conforming to NEMA AB1 HIC 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage690 V AC 50/60 Hz conforming to IEC 60947-2 750 V DC conforming to IEC 60947-2
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
32715 — Specifications
ParameterValue
Poles description3P
Trip unit nameSTR53UE F
Trip unit technologyElectronic
Device short nameCompact NS400H
StandardsIEC 60947-2
MPN
32715