Schneider Electric 34640
MPN34640
Obsolete
circuit breaker Compact NS125E - TMD - 125 A - 4 poles 3d
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product / component type | Circuit breaker |
| Device application | Distribution |
Mechanical
| Parameter | Value |
|---|---|
| Height | 161 mm |
| Width | 105 mm |
| Depth | 86 mm |
Electrical
| Parameter | Value |
|---|---|
| [In] rated current | 125 A at 40 °C |
| Breaking capacity | 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 21 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 750 V AC 50/60 Hz conforming to IEC 60947-2 |
Specifications
| Parameter | Value |
|---|---|
| Poles description | 4P |
| Trip unit name | TM-D |
| Trip unit technology | Thermal-magnetic |
| Device short name | Compact NS125E |
| Standards | IEC 60947-2 |
MPN
34640