Skip to main content
Schneider Electric 34641 — Molded Case Circuit Breakers (MCCB)

Schneider Electric 34641

MPN34641
Obsolete

circuit breaker Compact NS125E - TMD - 100 A - 4 poles 3d

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

34641 — Identification
ParameterValue
Product / component typeCircuit breaker
Device applicationDistribution
34641 — Mechanical
ParameterValue
Height161 mm
Width105 mm
Depth86 mm
34641 — Electrical
ParameterValue
[In] rated current125 A at 40 °C
Breaking capacity10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service breaking capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 21 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ue] rated operational voltage500 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage750 V AC 50/60 Hz conforming to IEC 60947-2
34641 — Specifications
ParameterValue
Poles description4P
Trip unit nameTM-D
Trip unit technologyThermal-magnetic
Device short nameCompact NS125E
StandardsIEC 60947-2
MPN
34641