Skip to main content
Schneider Electric 47292

Schneider Electric 47292

MPN47292
Active

Control unit MicroLogic 6.0E, MasterPact NT drawout, selective and earth fault protections (LSIG), energy meter

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

47292 key specifications
ParameterValue
Display typeDigital display
Network typeAC
Protection typefor overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Range of productMasterPact NT
Type of measurementEnergy meter
Product or component typeControl unit
Long-time protection delay adjustment type trAdjustable 9 settings
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Ground-fault protection time delay adjustment type tgAdjustable

All specifications

47292 additional specifications
ParameterValue
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Network frequency50/60 Hz
Poles4P 3P
Protected poles description4t 3t 3t + N/2
Communication of dataMeasurement readout Protection and alarm settings
Circuit breaker mounting modeDrawout
RangeMasterPact
Thermal memory20 mn
Trip unit nameMicroLogic 6.0 E
Local signalling3 LEDs (red) for electrical fault 1 LED (red) for internal error
Trip unit rating630 A at 50 °C 800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Trip unit protection functionsSelective + earth-fault protection
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range0.7...16.6 s at 7.2 x Ir 0.7...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir
[Ir] long-time protection pick-up adjustment range0.4...1 x In
[tsd] short-time protection delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ig] ground-fault protection pick-up adjustment range0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In 500...1200 A for In >= 1250 A
[Ii] instantaneous protection pick-up adjustment range2...15 x In Off
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
MPN
47292