Skip to main content
Schneider Electric 48093

Schneider Electric 48093

MPN48093
Active

circuit breaker Masterpact NW40H2 - 4000 A - 3 poles - fixed - w/o trip unit

$14,868.92Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

48093 key specifications
ParameterValue
Control typePush-button
Performance typeH2 100 kA 440 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current85 kA 1 s 75 kA 3 s
Current4000 A at 40 °C
[Ics] rated service breaking capacity100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity220 kA 220/415 V AC at 50/60 Hz 187 kA 440 V AC at 50/60 Hz 187 kA 525 V AC at 50/60 Hz 187 kA 690 V AC at 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
Power dissipation in650 W

All specifications

48093 additional specifications
ParameterValue
Poles description3P
IP degree of protectionIP30 conforming to IEC 60529
Mounting modeFixed
Mounting supportBackplate Rails
Connection pitch150 mm
Upside connectionRear
Downside connectionRear
Maximum closing response time70 ms
Pollution degree4 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Depth297 mm
Width422 mm
Height352 mm
Electrical durability5000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3
Mechanical durability10000 cycles without maintenance 20000 cycles with maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2
RangeMasterPacT
Control unitWithout control unit
Sensor rating2000 A 4000 A
Device applicationPower distribution protection
Circuit breaker nameMasterPact NW40H2
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
Integrated instantaneous protection (DIN in kA peak)171...209 kA
MPN
48093