Specifications

48336 key specifications
ParameterValue
Control typePush-button
Performance typeH1 100 kA 440 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current100 kA 1 s 100 kA 3 s
Current4000 A at 40 °C
[Ics] rated service breaking capacity100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz 100 kA at 690 V AC 50/60 Hz
[Icm] rated short-circuit making capacity220 kA 220/415 V AC at 50/60 Hz 220 kA 440 V AC at 50/60 Hz 220 kA 525 V AC at 50/60 Hz 220 kA 690 V AC at 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity100 kA at 220/415 V AC 50/60 Hz 100 kA at 440 V AC 50/60 Hz 100 kA at 525 V AC 50/60 Hz 100 kA at 690 V AC 50/60 Hz
Power dissipation in550 W

All specifications

48336 additional specifications
ParameterValue
Poles description3P
IP degree of protectionIP30 conforming to IEC 60529
Mounting modeDrawout
Mounting supportBackplate Rails
Connection pitch230 mm
Upside connectionRear
Downside connectionRear
Maximum closing response time80 ms
Pollution degree4 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Depth395 mm
Width786 mm
Height479 mm
Electrical durability1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-2 AC-23A: 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3 AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to EN/IEC 60947-3
Mechanical durability10000 cycles with maintenance 5000 cycles without maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2
RangeMasterPacT
Control unitWithout control unit
Sensor rating2000 A 4000 A
Device applicationPower distribution protection
Circuit breaker nameMasterPact NW40bH1
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes conforming to EN/IEC 60947-2
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
MPN