Skip to main content
Schneider Electric 48350 — Air Circuit Breakers

Schneider Electric 48350

MPN48350
Active

switch-disconnector Masterpact NW63HA - 6300 A - 690 V - 3 poles - drawout

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

48350 — Identification
ParameterValue
Product typeSwitch disconnector
Product nameMasterPact NW
RangeMasterPacT
ApplicationProtection
48350 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)6300 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3
48350 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)85 kA during 1 s conforming to IEC 60947-3 85 kA during 3 s conforming to IEC 60947-3
Rated short-circuit making capacity (Icm)187 kA 220...690 V AC at 50/60 Hz
Breaking capacity codeHA
48350 — Performance
ParameterValue
Mechanical durability (cycles)10000 cycles with maintenance conforming to IEC 60947-3 5000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 1500 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 1500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
48350 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportChassis
Contact position indicatorYes
Width767 mm
Height352 mm
Depth297 mm
Connection pitch230 mm
48350 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-35...85 °C
Pollution degree4 conforming to IEC 60664-1
48350 — Approvals
ParameterValue
StandardsIEC 60947-3
MPN
48350