Schneider Electric 48361

Schneider Electric 48361

MPN48361
Active

control unit Micrologic 6.0 A, for Masterpact NW drawout, LSIG protections

$1,308.33Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

48361 key specifications
ParameterValue
Display typeDigital display
Network typeAC
Protection typefor overload protection (long time) for short time short-circuit protection for instantaneous short-circuit protection for earth fault
Range of productMasterPact NW
Type of measurementAmmeter
Product or component typeControl unit
Long-time protection delay adjustment type trAdjustable 9 settings
Short-time protection delay adjustment type tsdAdjustable
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Ground-fault protection pick-up adjustment type igAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiAdjustable 9 settings
Ground-fault protection time delay adjustment type tgAdjustable

All specifications

48361 additional specifications
ParameterValue
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Network frequency50/60 Hz
Poles4P 3P
Protected poles description4t 3t 3t + N/2
Communication of dataMeasurement readout Protection and alarm settings
Circuit breaker mounting modeDrawout
RangeMasterPact
Thermal memory20 mn
Trip unit nameMicroLogic 6.0 A
Local signalling3 LEDs (red) for electrical fault 1 LED (red) for internal error
Trip unit rating800 A at 50 °C 1000 A at 50 °C 1250 A at 50 °C 1600 A at 50 °C 2000 A at 50 °C 2500 A at 50 °C 3200 A at 50 °C 4000 A at 50 °C 5000 A at 50 °C 6300 A at 50 °C
Device applicationDistribution
Trip unit technologyElectronic
Earth-leakage protectionWithout
Trip unit protection functionsSelective + earth-fault protection
Zone selective interlocking ZSIWith
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range0.7...16.6 s at 7.2 x Ir 0.7...24 s at 6 x Ir 12.5...600 s at 1.5 x Ir
[Ir] long-time protection pick-up adjustment range0.4...1 x In
[tsd] short-time protection delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ig] ground-fault protection pick-up adjustment range0.2...1 x In for 400 A < In < 1250 A 0.3...1 x In for In 500...1200 A for In >= 1250 A
[Ii] instantaneous protection pick-up adjustment range2...15 x In Off
[Tg] Ground-Fault protection time delay adjustment range0...0.4 s I²t=off 0.1...0.4 s I²t=on
MPN
48361