Residual current protection relay, VigiPacT RH10P, 300mA, 380/415VAC 50/60Hz, front panel mounting

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

56245 key specifications
ParameterValue
Type of measurementEarth fault current internal measurement, range: 80...100 %
Product or component typeResidual current protection relay
Residual earth-leakage sensitity adjustment typeFixed
Supply voltage380...415 V AC 50/60 Hz 55...110 %
[Uimp] rated impulse withstand voltage8 kV
Current sensors compatibilityVigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current8 A
Power consumption in4 VA
IK degree of protectionIK07 conforming to EN 50102
IP degree of protectionIP40 on front face: conforming to EN/IEC 60529 IP30 on side parts: conforming to EN/IEC 60529 IP20 on connection terminals: conforming to EN/IEC 60529
Mounting supportFront panel
Wire stripping lengthAuxiliary power supply: 7 mm Fault: 7 mm Relay test and fault reset: 7 mm Sensor: 7 mm Voltage presence: 7 mm

All specifications

56245 additional specifications
ParameterValue
Connections - terminalsAuxiliary power supply: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Auxiliary power supply: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Fault: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Fault: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Fault: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Relay test and fault reset: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Sensor: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Sensor: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² flexible AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.2...2.5 mm² rigid AWG 24...AWG 12 Voltage presence: terminal block cable(s) 0.25...2.5 mm² flexible AWG 24...AWG 12
Pollution degree3 conforming to IEC 60664-1
Relative humidity95 % at 55 °C
Electrical shock protection classClass II
Depth78 mm
Width72 mm
Height72 mm
Product weight0.3 kg
Cut-out dimensions68 x 68 mm
StandardsEN/IEC 60947-2 Annex M EN/IEC 60755 UL 1053 CAN/CSA C22.2 No. 144
RangeVigiPacT
ResetManual reset
MonitoringElectronics (continuous) Power supply (continuous) Relay/sensor link (continuous)
Minimum load10 mA at 12 V
Test functionLocal Remote test
Earthing systemTN-S IT TT
Device short nameRH10P
Relay applicationProtection relay
Tightening torqueAuxiliary power supply: 0.6 N.m Fault: 0.6 N.m Relay test and fault reset: 0.6 N.m Sensor: 0.6 N.m Voltage presence: 0.6 N.m
Overvoltage categoryIV
Mechanical robustnessFire resistance conforming to IEC 60695-2-1 IK protection 2 joules: IK07 conforming to EN 50102 Vibrations 13.2...100 Hz: 0.7 g Vibrations 2...13.2 Hz: +/- 1 mm
Tamperproof of settingsProtected by sealable cover
Earth-leakage time delayInstantaneous
Earth-leakage sensitivity0.3 A
Electromagnetic compatibilityConducted and radiated emissions: , B, conforming to CISPR 11 Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6 Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2 High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5 Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4 Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Monitored distribution system1000 V - AC at 50/60 Hz (maximum) 1000 V - AC at 400 Hz (maximum)
Earth-leakage protection classType A
Ambient air temperature for storage-55...85 °C
Ambient air temperature for operation-35...70 °C