Rated 16 A at 250 V AC 50 Hz, it switches a single-pole normally-open (1 NO) contact. Control is via a 230 V AC 50 Hz impulse signal drawing 19 VA during the 50 ms pulse. The relay is rated for 200,000 cycles under AC-22 duty (resistive and mixed loads up to 16 A).
Mounts on a DIN rail, occupies an 18 mm width (one modular pitch). The 87 mm height and 69 mm depth fit standard distribution boards. IP40 when installed in an enclosure. Tunnel-type terminals accept up to 4 mm² rigid or 2.5 mm² flexible cable — sized for standard lighting or small motor contactor control circuits.
The 16 A rated current at 250 V AC is the continuous thermal current (Ith) for resistive loads — this relay can switch lighting banks, contactor coils, or solenoid valves within that limit. The AC-22 electrical durability of 200,000 cycles means it's rated for mixed resistive and inductive loads up to 16 A, not just resistive. The 5 switching operations per minute maximum is a thermal limit on the coil — don't pulse it faster than every 12 seconds in continuous use. The 2.5 kV impulse withstand voltage (Uimp) gives it adequate margin for 230/400 V distribution systems.