Skip to main content
Schneider Electric A9D06840

Schneider Electric A9D06840

MPNA9D06840
Active

Acti9 iC60H RCBO plug on neutral - 1P+Ns - 40A - C - 10000A - 100mA - type A

$210.93Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D06840 key specifications
ParameterValue
Control typeToggle
Network typeAC
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Voltage400 V AC 50/60 Hz
[Ue] rated operational voltage230/240 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current250 A
Breaking capacity10000 A Icn at 240 V AC 50/60 Hz conforming to IEC 61009-2-2
Current40 A at 50 °C
Residual current tripping technologyVoltage dependent
[Ics] rated service breaking capacity7500 A at 240 V AC 50/60 Hz conforming to IEC 61009-2-2
Network frequency50/60 Hz

All specifications

A9D06840 additional specifications
ParameterValue
Poles description1P + Ns
Number of protected poles1
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Mounting modePlug-on
Mounting supportIsobar B Isobar A
Wire stripping length14 mm for top connection 13 mm for bottom connection
Connections - terminalsScrew clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)
Relative humidity95 % at 55 °C
Depth72 mm
Width18 mm
ColorWhite
Height110 mm
Electrical durability5000 cycles
Mechanical durability20000 cycles
StandardsBS EN 61009-1 IEC 61009-1 IEC 61009-2-2
RangeActi9
Curve codeC
9 mm pitches2
Earthing systemTN
Tropicalisation2
Limitation class3
Local signallingON/OFF indication Fault indication
Neutral positionLeft
Device short nameiC60H RCBO PoN
Tightening torque3.5 N.m top 2 N.m bottom
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Magnetic tripping limit5...10 x In
Earth-leakage protectionIntegrated
Device location in systemOutgoer
Earth-leakage sensitivity100 mA
Suitability for isolationYes
Contact position indicatorYes
Circuit breaker applicationDistribution
Electrical insulation classClass II
Locking options descriptionPadlock in on or off position
Earth-leakage protection classType A
Ambient air temperature for storage-40...85 °C
Earth-leakage protection time delayInstantaneous
Ambient air temperature for operation-15...60 °C
Comb busbar and distribution block compatibilityNO
MPN