Skip to main content
Schneider Electric A9D16816 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D16816 Acti9 IKQE RCBO, 16 A, 10 kA, 10

MPNA9D16816
Obsolete

Schneider Electric Acti9 IKQE RCBO, 1P+N, 16 A at 50 °C, 10 kA Icn, 10 mA earth-leakage, thermal-magnetic, DIN-rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D16816 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)10 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D16816 — Electrical Ratings
ParameterValue
Rated current (In)16 A at 50 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D16816 — Identification
ParameterValue
Product nameIKQE RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D16816 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end
Wire stripping lengthPower circuit: 13 mm for top or bottom connection
Terminal tightening torquePower circuit: 2 N.m top or bottom
Width18 mm
Height118 mm
Depth82 mm
A9D16816 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D16816 — Approvals
ParameterValue
StandardsBS EN 61009-1

Product details

The Schneider Electric A9D16816 is an Acti9 IKQE RCBO — a combined residual current breaker with overcurrent protection in a 1P+N format, rated 16 A at 50 °C with a 10 mA earth-leakage sensitivity and a 10 kA Icn breaking capacity at 230 V AC. The thermal-magnetic trip unit handles both overload and short-circuit curves, with a C-curve characteristic.

The 118 mm height and 82 mm depth fit standard distribution board cutouts. Tunnel-type terminals accept 1–16 mm² rigid cable or 1–10 mm² flexible with or without ferrules; the tightening torque is 2 N·m for the power circuit. Wire stripping length is 13 mm for top or bottom connection. Neutral is on the left.

Frequently asked questions

What is the A9D16816's breaking capacity?

10,000 A Icn at 230 V AC, 50/60 Hz.

What earth-leakage sensitivity does the A9D16816 have?

10 mA, suitable for personnel protection in TN systems.

MPN
A9D16816