Product identification and compliance
It carries a 20 A rated current at 50 °C and a 10 mA earth-leakage sensitivity, with a C-curve trip characteristic. The breaking capacity is 10 000 A Icn at 230 V AC, 50/60 Hz. Compliance is to BS EN 61009-1, making it suitable for UK and IEC markets. The unit is designed for TN earthing systems and is rated IP20 for indoor panel installation.
Tunnel-type terminals accept 1…16 mm² rigid or 1…10 mm² flexible conductors; tightening torque is 2 N.m. The device is padlockable with a 4 mm diameter padlock. For panel builders, the 82 mm depth and 118 mm height fit standard distribution board cutouts.