It is rated at 16 A (C-curve) with 30 mA earth leakage sensitivity and a breaking capacity of 10 000 A Icn at 230 V AC, 50/60 Hz (cite:,). The 30 mA leakage threshold provides personal protection against direct contact faults (cite:).
Clip-on mounting to DIN rail (cite:). The unit occupies 2 x 9 mm pitches (18 mm width per pole) (cite:,). Neutral is on the left (cite:). Tunnel-type terminals accept 1 to 16 mm² rigid cable without ferrules, or 1 to 10 mm² flexible with or without cable end (cite:). Tightening torque for the power circuit is 2 N.m (cite:). Wire strip length is 13 mm for top or bottom connection (cite:). The device is padlockable with a Ø 4 mm padlock for lockout/tagout (cite:).
Designed to BS EN 61009-1 (cite:). Suitability for isolation is confirmed (cite:). Tropicalisation class 2 indicates protection against damp heat (cite:). The device is rated for TN earthing systems (cite:).