Skip to main content
Schneider Electric A9D18825 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D18825 IKQE RCBO, 25 A, 100 mA, Curve C

MPNA9D18825
Obsolete

Schneider Electric Acti9 IKQE RCBO, 1P+N, 25 A, 100 mA, curve C, 10 kA Icn at 230 V AC, BS EN 61009-1, DIN rail clip-on.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D18825 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D18825 — Electrical Ratings
ParameterValue
Rated current (In)25 A at 50 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D18825 — Identification
ParameterValue
Product nameIKQE RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D18825 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end
Wire stripping lengthPower circuit: 13 mm for top or bottom connection
Terminal tightening torquePower circuit: 2 N.m top or bottom
Width18 mm
Height118 mm
Depth82 mm
A9D18825 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D18825 — Approvals
ParameterValue
StandardsBS EN 61009-1

Product details

It combines a 25 A thermal-magnetic MCB (curve C) with integrated 100 mA earth-leakage protection, all in a 1P+N form factor with neutral on the left. Rated 25 A at 50 °C, so no derating headache in a warm enclosure as long as ambient stays under that. The 100 mA earth-leakage threshold is a common choice for circuits supplying equipment where nuisance tripping from a 30 mA device would be a problem — think fixed machinery, lighting banks, or sub-distribution where personnel contact is unlikely but ground-fault protection is still code-required.

Panel integration

The tunnel-type terminals accept 1 to 16 mm² rigid cable (1 to 10 mm² flexible with or without ferrule), and the tightening torque is 2 N·m. Wire strip length is 13 mm. IP20 rated — fine for a distribution board or enclosed panel, not for wet environments. Padlockable with a Ø4 mm padlock for lockout/tagout.

Rated for 5,000 electrical cycles and 20,000 mechanical cycles. That is a standard duty class for a distribution RCBO — not a heavy-switching device, but adequate for its role as a protective device that operates only under fault or manual isolation. The toggle provides ON/OFF indication and a contact position indicator confirms the state of the main contacts.

Frequently asked questions

What is the A9D18825 used for?

It is a combined residual current breaker and overcurrent protection device (RCBO) for 1P+N distribution circuits, providing 25 A overcurrent protection (curve C) and 100 mA earth-leakage protection in a single 18 mm DIN-rail module.

What standard does the A9D18825 comply with?

It is certified to BS EN 61009-1, the harmonized standard for RCBOs covering both overcurrent and residual-current protection.

MPN