Skip to main content
Schneider Electric A9D18832 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D18832 IKQE RCBO, 32 A, 10 kA, 100 mA,

MPNA9D18832
Obsolete

Schneider Electric Acti9 IKQE RCBO, 1P+N, 32 A, 10 kA, 100 mA, Curve C, thermal-magnetic, DIN rail, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D18832 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)100 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D18832 — Electrical Ratings
ParameterValue
Rated current (In)32 A at 50 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D18832 — Identification
ParameterValue
Product nameIKQE RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D18832 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end
Wire stripping lengthPower circuit: 13 mm for top or bottom connection
Terminal tightening torquePower circuit: 2 N.m top or bottom
Width18 mm
Height118 mm
Depth82 mm
A9D18832 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D18832 — Approvals
ParameterValue
StandardsBS EN 61009-1

Product details

It protects a 1P+N circuit at 32 A rated current (50 °C ambient) with a 10 kA breaking capacity at 230 V AC, and adds integrated earth-leakage protection set at 100 mA sensitivity.

The 32 A rating at 50 °C means this RCBO carries a full 32 A load continuously at typical panel ambient temperatures without derating — useful for final subcircuits feeding socket outlets or fixed equipment in distribution boards. The 100 mA earth-leakage sensitivity is a deliberate choice — it's less sensitive than the typical 30 mA used for personal protection, so it's better suited for circuits where some natural leakage is expected (long cable runs, multiple IT loads) and the priority is fire protection or equipment protection rather than shock prevention. Thermal-magnetic trip technology means the thermal bimetal handles overloads (slow, inverse-time) and the solenoid handles short-circuits (instantaneous). No electronics to fail, no auxiliary power needed for the trip function.

Tunnel terminals accept 1–16 mm² rigid or 1–10 mm² flexible cable; tighten to 2 N·m. Rated for TN earthing systems only. The device is intended as an outgoer in the distribution board — not a main switch. It is suitable for isolation (full contact position indicator and padlockable with a Ø4 mm padlock). Electrical durability is 5,000 cycles; mechanical durability 20,000 cycles. For a final-circuit RCBO switched infrequently (once a week or less) that's a long service life; for frequent switching duty (daily on/off) consider a contactor instead.

Frequently asked questions

Where can I buy the A9D18832 and get a price?

The A9D18832 is sourced to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is the A9D18832's breaking capacity?

10,000 A Icn at 230 V AC, 50/60 Hz — sufficient for most final-distribution fault levels in TN systems.

What standard does the A9D18832 comply with?

It is certified to BS EN 61009-1, the harmonized standard for RCBOs combining overcurrent and residual current protection.

MPN
A9D18832