What ships in the box
Rated 16 A with a C-curve magnetic trip (5–10 x In) and integrated 30 mA earth-leakage protection, it breaks fault currents up to 6000 A Icn at 380–415 V AC per EN/IEC 61009-2-1. No separate RCD block to order — the leakage detection is built in.
Panel fit and fill factor
This RCBO occupies 10 x 9 mm pitches (90 mm wide) on the DIN rail, with a depth of 78.5 mm and height of 91 mm.
Selectivity and coordination
Pollution degree 3 (industrial environment, conductive or dry non-conductive pollution). IP20 on the device body, IP40 inside a modular enclosure. Rated for 90 % relative humidity at 55 °C. The standards listing is EN/IEC 61009-2-1 — the harmonized RCBO standard covering overcurrent and residual-current protection.