The integrated 30 mA earth-leakage protection covers the standard personnel-protection threshold per IEC 61009-2-1, so this single device serves both overcurrent and residual-current duty on a 3P+N outgoing circuit.
Breaking capacity is 6000 A Icn at 380–415 V AC, 50/60 Hz, conforming to EN/IEC 61009-2-1. Limitation class 3 per the same standard means it limits let-through energy enough to protect downstream wiring and loads under short-circuit conditions, which helps with coordination in a panel.
Tunnel terminals accept 0.75–16 mm² rigid or 0.33–10 mm² flexible (with or without ferrule).
No official successor or direct cross-reference is recorded — this is the current catalog number for the 25 A, 30 mA, C-curve, 3P+N DPN Vigi configuration.