Skip to main content
Schneider Electric A9D31845 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D31845 Acti9 iC60 RCBO, 45 A, 30 mA, B

MPNA9D31845
Active

Schneider Electric Acti9 iC60H RCBO, A9D31845, 1P+Ns, 45 A, B curve, 30 mA earth leakage, 10 kA Icn at 230/240 V AC.

$186.69Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D31845 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D31845 — Electrical Ratings
ParameterValue
Rated current (In)45 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D31845 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO
A9D31845 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...25 mm² rigid without cable end Screw clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...16 mm² rigid without cable end Screw clamp terminal (bottom) 1...10 mm² flexible
Wire stripping lengthPower circuit: 13 mm for bottom connection Power circuit: 14 mm for top connection
Terminal tightening torquePower circuit: 3.5 N.m top Power circuit: 2 N.m bottom
Width18 mm
Height110 mm
Depth77.5 mm
A9D31845 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D31845 — Approvals
ParameterValue
StandardsBS EN 61009-1 IEC 61009-2-2 AS/NZS 61009.1 IEC 61009-1

Product details

The Schneider Electric A9D31845 is an Acti9 iC60H RCBO — a combined residual current breaker with overcurrent protection in a single 18 mm wide module. It carries a 45 A rated current at 50 °C with a B curve trip characteristic, integrated 30 mA earth-leakage protection, and a 10 kA breaking capacity at 230/240 V AC. That 10 kA Icn rating means it can safely interrupt fault currents up to 10,000 A without upstream damage — sized for final subcircuits in TN earthing systems where the prospective short-circuit current stays under that threshold.

Clip-on mounting to DIN rail, 2 x 9 mm pitches wide (18 mm total). Neutral on the left, single pole protected.

Frequently asked questions

How do I get current pricing and availability for A9D31845?

Submit an RFQ through the storefront; availability and current pricing are confirmed at quote time through independent distribution.

What is A9D31845's listed depth?

77.5 mm depth on a 110 mm high, 18 mm wide module — standard single-module RCBO footprint.

What is A9D31845's listed range?

Part of the Acti9 range, specifically the iC60H RCBO series.

What compliance documentation does this brand provide for A9D31845?

Certified to BS EN 61009-1, IEC 61009-2-2, AS/NZS 61009.1, and IEC 61009-1.

MPN