The A9D35610: The 10 A rated current (In) with C-curve magnetic tripping (5–10 x In) means it holds momentary inrush from small motor or lighting loads but trips fast on a hard short — standard for general-purpose distribution in residential and light commercial panels. The 4500 A Icn breaking capacity at 230–240 V AC is the maximum fault current it can safely interrupt; that is adequate for most sub-distribution boards but check your point-of-supply SCCR if feeding from a high-capacity transformer. The 30 mA earth-leakage sensitivity provides personal protection (additional protection per IEC 60364) and is the most common threshold for socket-outlet circuits.
Clip-on mounting to DIN rail, 36 mm width (4 x 9 mm pitches), neutral on the left. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible; strip length 15 mm, tighten to 2 N·m. IP20 finger-safe with the modular enclosure (IP40 in the enclosure). The toggle gives local ON/OFF/trip indication.