What this RCBO does in the panel
It protects a single-phase outgoing circuit (1P+N, neutral left) against overload, short-circuit, and earth leakage in one unit, saving a DIN-rail position versus separate MCB and RCCB. Rated at 6 A with a type B tripping curve, it is sized for lighting, socket outlets, or small control circuits where the inrush is modest and nuisance tripping on cable charging is not a concern. The 30 mA earth-leakage sensitivity provides additional shock protection for personnel in TN earthing systems. The limitation class 3 rating means it lets through less fault energy than a standard breaker, helping downstream selectivity.
Tunnel-type terminals accept 1 to 16 mm² rigid cable or 1 to 10 mm² flexible (with or without ferrule); strip length is 13 mm. IP20 rated — suitable for installation inside a distribution board or enclosure. The toggle control provides local ON/OFF indication, and the contact position indicator confirms the state of the main contacts. A padlock with Ø 4 mm shackle can lock the toggle in the OFF position for isolation during maintenance.