Specifications

A9D37840 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication
A9D37840 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 50 °C
Rated operational voltage (Ue)230 V AC 50/60 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D37840 — Identification
ParameterValue
Product nameIKQE RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
A9D37840 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsTunnel type terminal (top or bottom) 1...16 mm² rigid without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible without cable end Tunnel type terminal (top or bottom) 1...10 mm² flexible with cable end
Wire stripping lengthPower circuit: 13 mm for top or bottom connection
Terminal tightening torquePower circuit: 2 N.m top or bottom
Width18 mm
Height118 mm
Depth82 mm
A9D37840 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20
Relative humidity95 % at 55 °C
Tropicalisation2
A9D37840 — Approvals
ParameterValue
StandardsBS EN 61009-1

Product details

It integrates both earth-leakage detection at 30 mA sensitivity and thermal-magnetic overcurrent protection rated at 40 A, all within a single 18 mm wide module that clips onto a DIN rail.

Neutral is on the left, line on the right. Tunnel-type terminals accept 1–16 mm² rigid or 1–10 mm² flexible conductors (with or without ferrules); strip length is 13 mm and tightening torque is 2 N·m. The toggle actuator provides local ON/OFF indication and the unit is padlockable with a 4 mm Ø padlock for lockout/tagout. The tropicalisation class 2 means it's treated against humidity and fungus, and the 95 % RH at 55 °C rating confirms it handles warm, damp environments typical of industrial enclosures.

Frequently asked questions

Where can I buy the A9D37840 and get a price?

The A9D37840 is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9D37840?

10 kA Icn at 230 V AC, 50/60 Hz — sufficient for most residential and light commercial distribution boards.

What standard does the A9D37840 comply with?

It complies with BS EN 61009-1, the harmonized European standard for RCBOs.

What is the A9D37840's depth?

82 mm — this is the body depth, not including the toggle actuator throw.

MPN