What this RCBO covers
The 20 A rated current (In) and C-curve mean this breaker holds up to 20 A continuous and trips magnetically between 5 and 10 times that (100–200 A) — typical for general-purpose socket outlets and lighting circuits where inrush from small motors or capacitive loads is moderate. The 6000 A Icn breaking capacity at 230...240 V AC (EN/IEC 61009-2-1) is the standard domestic / light commercial fault-interruption rating; if your available fault current exceeds 6 kA at the panel, you need a current-limiting upstream device or a higher-rated breaker.
Clip-on mounting to DIN rail (35 mm), 4 modules wide at 9 mm pitch (36 mm total width). Neutral on the left, phase on the right. IP20 finger-safe face; IP40 inside the modular enclosure. Tightening torque 2 N.m.
Listed as current production (active lifecycle stage). No successor or phase-out notice on record.