Skip to main content
Schneider Electric A9D41620 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D41620 Acti9 iDPN Vigi RCBO, 20 A, C-cu

MPNA9D41620
Active

Schneider Electric Acti9 iDPN Vigi RCBO, 1P+N, 20 A, C-curve, 6000 A Icn, 300 mA earth leakage, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D41620 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D41620 — Electrical Ratings
ParameterValue
Rated current (In)20 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D41620 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPN N Vigi
A9D41620 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D41620 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D41620 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

What this RCBO covers

The 20 A rated current (In) and C-curve mean this breaker holds up to 20 A continuous and trips magnetically between 5 and 10 times that (100–200 A) — typical for general-purpose socket outlets and lighting circuits where inrush from small motors or capacitive loads is moderate. The 6000 A Icn breaking capacity at 230...240 V AC (EN/IEC 61009-2-1) is the standard domestic / light commercial fault-interruption rating; if your available fault current exceeds 6 kA at the panel, you need a current-limiting upstream device or a higher-rated breaker.

Clip-on mounting to DIN rail (35 mm), 4 modules wide at 9 mm pitch (36 mm total width). Neutral on the left, phase on the right. IP20 finger-safe face; IP40 inside the modular enclosure. Tightening torque 2 N.m.

Listed as current production (active lifecycle stage). No successor or phase-out notice on record.

Frequently asked questions

What is the breaking capacity of A9D41620?

6000 A Icn at 230...240 V AC 50 Hz, conforming to EN/IEC 61009-2-1.

What earth-leakage sensitivity does A9D41620 have?

300 mA residual-current protection, integrated into the RCBO.

MPN
A9D41620