The Schneider Electric A9D41632 is an Acti9 iDPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — one module wide at 36 mm, single-pole plus neutral, rated 32 A with a C-curve magnetic trip characteristic (5 to 10 times In). It carries a 6000 A Icn breaking capacity at 230...240 V AC 50 Hz, compliant with EN/IEC 61009-2-1, and integrates 300 mA earth-leakage protection on the outgoing circuit.
The 32 A thermal-magnetic trip unit handles general-purpose distribution loads — lighting, socket outlets, small appliances — on a 50 Hz AC network. Integrated 300 mA residual-current detection covers the outgoing circuit without a separate RCCB upstream — saves a DIN module and one wiring step.
Clip-on mounting to DIN rail, 4 pitches of 9 mm between phase and neutral terminals. Accepts rigid cable up to 16 mm² or flexible up to 10 mm² (with or without ferrule). Neutral is on the left, which matters for busbar orientation in a multi-pole assembly.