Specifications

A9D41732 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)300 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D41732 — Electrical Ratings
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D41732 — Identification
ParameterValue
Product nameActi9 DPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDPN N Vigi
A9D41732 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules10
Terminal connectionsTunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width90 mm
Height91 mm
Depth78.5 mm
A9D41732 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity90 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D41732 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The Schneider Electric A9D41732 is an Acti9 DPN Vigi residual-current circuit breaker with overcurrent protection (RCBO) — a single module combining a 32 A thermal-magnetic MCB and a 300 mA earth-leakage detector in a 3P+N, 18 mm per-phase pitch package. The 32 A rated current (In) and C-curve magnetic trip (5–10 × In) mean it handles moderate inrush from motor or lighting loads without nuisance tripping, while the 300 mA sensitivity covers earth faults on circuits where 30 mA would cause unwanted trips — common for distribution sub-feeds or equipment with natural leakage. The limitation class 3 rating means it limits let-through energy enough to coordinate with upstream devices in a selective scheme.

Clip-on mounting on a DIN rail, 9 module pitches wide (90 mm). Neutral is on the left; tunnel terminals accept 0.75–16 mm² rigid or 0.33–10 mm² flexible conductors. The IP20 enclosure (IP40 in modular enclosure) suits clean indoor panels. Local signalling shows ON, OFF, and fault-trip status via the toggle. The toggle itself is the control type — no remote shunt trip or auxiliary contact built in, so plan for external indication if needed.

Frequently asked questions

What is A9D41732's listed depth (78.5 mm) on this component line?

The A9D41732 has a depth of 78.5 mm, a width of 90 mm, and a height of 91 mm.

What is A9D41732's listed range (Acti9) on this component line?

The A9D41732 belongs to the Schneider Acti9 range, specifically the Acti9 DPN Vigi product name.

MPN
A9D41732