Skip to main content
Schneider Electric A9D54640 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D54640 Acti9 iDPN Vigi, 40A B-Curve 30m

MPNA9D54640
Obsolete

Schneider Electric Acti9 iDPN Vigi, RCBO, 1P+N, 40 A, B-curve, 30 mA earth-leakage, 4.5 kA Icn, DIN rail, white.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9D54640 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D54640 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)230...240 V AC 50 Hz
Poles description1P + N
Neutral pole positionLeft
Network typeAC
Network frequency50 Hz
Rated insulation voltage (Ui)400 V AC 50 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability10000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D54640 — Identification
ParameterValue
Product nameActi9 iDPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiDPNa Vigi
A9D54640 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules4
Terminal connectionsSingle terminal top or bottom 1...16 mm² rigid Single terminal top or bottom 1...10 mm² flexible Single terminal top or bottom 1...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width36 mm
Height85 mm
Depth73 mm
A9D54640 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity95 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D54640 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

The A9D54640: The B-curve (magnetic tripping between 3 and 5 x In) means the unit trips instantaneously at 120–200 A — suited for resistive and general-purpose loads, not high-inrush motor circuits. The 30 mA earth-leakage sensitivity provides personnel protection (residual current device function) per IEC 61009-2-1. The thermal-magnetic trip unit handles the overcurrent side; the integrated earth-leakage block shares the same compact housing. IP20 on the front, IP40 inside a modular enclosure — standard for panel-mount gear.

Frequently asked questions

What is the breaking capacity of A9D54640?

The A9D54640 has a breaking capacity of 4500 A Icn at 230...240 V AC 50 Hz, conforming to EN/IEC 61009-2-1.

What earth-leakage sensitivity does A9D54640 provide?

The A9D54640 integrates earth-leakage protection with a sensitivity of 30 mA.

Where can I buy A9D54640?

The A9D54640 is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
A9D54640