ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
Trip unit technologyThermal-magnetic
Local signalling / indicationON, OFF, fault trip
A9D55710 — Electrical Ratings
ParameterValue
Rated current (In)10 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description3P + N
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryIII conforming to IEC 60364
Device location in systemOutgoer
Electrical durability20000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D55710 — Identification
ParameterValue
Product nameActi9 DPN Vigi
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameDPN N Vigi
A9D55710 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules10
Terminal connectionsTunnel type terminal top or bottom 0.75...16 mm² rigid Tunnel type terminal top or bottom 0.33...10 mm² flexible Tunnel type terminal top or bottom 0.33...10 mm² flexible with ferrule
Wire stripping length15 mm for top or bottom connection
Terminal tightening torque2 N.m top or bottom
Width90 mm
Height91 mm
Depth78.5 mm
A9D55710 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-30...70 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
Relative humidity90 % at 55 °C
Tropicalisation2 conforming to IEC 60068-1
A9D55710 — Approvals
ParameterValue
StandardsEN/IEC 61009-2-1

Product details

Rated 10 A with a B-curve magnetic trip (3 to 5 x In) and 30 mA earth-leakage sensitivity, it protects outgoing circuits against overload, short-circuit, and ground faults in one DIN-rail unit. Poles are 3P+N with neutral on the left; the thermal-magnetic trip is limitation class 3, meaning it limits let-through energy enough to protect downstream equipment in most distribution panels.

Clip-on DIN-rail mount, 9 module pitches wide (90 mm). The 18 mm phase-to-neutral pitch matches the standard Acti9 busbar grid. IP20 on the terminals, IP40 inside the modular enclosure — fine for dry indoor panels, not for washdown areas.

Frequently asked questions

Where can I buy A9D55710 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current availability and pricing.

What are the key ratings for A9D55710?

Rated 10 A, B-curve (3-5 x In magnetic trip), 30 mA earth-leakage sensitivity, 6 kA breaking capacity at 400 V AC, 3P+N, thermal-magnetic trip, limitation class 3.

What is the depth of A9D55710?

The depth is 78.5 mm, which fits standard distribution board enclosures with 80 mm or deeper back boxes.

What standards does A9D55710 comply with?

It complies with EN/IEC 61009-2-1 for RCBOs, overvoltage category III per IEC 60364, and pollution degree 3. Tropicalisation class 2 per IEC 60068-1.