Skip to main content
Schneider Electric A9D56806 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9D56806 Acti9 iC60 RCBO, 6 A, B Curve, 1

MPNA9D56806
Active

Schneider Electric Acti9 iC60 RCBO, 1P+N, 6 A, B curve, 10 kA, 30 mA, thermal-magnetic, IP20, white.

$197.56Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9D56806 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage dependent
Trip unit technologyThermal-magnetic
Local signalling / indicationON/OFF indication Fault indication
A9D56806 — Electrical Ratings
ParameterValue
Rated current (In)6 A at 50 °C
Rated operational voltage (Ue)230/240 V AC 50/60 Hz
Poles description1P + Ns
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)400 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Overvoltage categoryII
Device location in systemOutgoer
Electrical durability5000 cycles
Mechanical durability (operating cycles)20000 cycles
A9D56806 — Identification
ParameterValue
Product nameActi9 iC60 RCBO
Product / component typeResidual current breaker with overcurrent protection (RCBO)
Product range / familyActi9
Device short nameiC60H RCBO PoN
A9D56806 — Mechanical
ParameterValue
Mounting supportIsobar A Isobar B
Mounting modePlug-on
Control typeToggle
Width in 9 mm modules2
Terminal connectionsScrew clamp terminal (top) 1...16 mm² flexible Screw clamp terminal (bottom) 1...10 mm² flexible Screw clamp terminal (top) 1...25 mm² rigid Screw clamp terminal (bottom) 1...16 mm² rigid Plug-on neutral (upstream)
Wire stripping length14 mm for top connection 13 mm for bottom connection
Terminal tightening torque3.5 N.m top 2 N.m bottom
Width18 mm
Height110 mm
Depth72 mm
A9D56806 — Environmental
ParameterValue
Operating ambient temperature-15...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Relative humidity95 % at 55 °C
Tropicalisation2
A9D56806 — Approvals
ParameterValue
StandardsBS EN 61009-1 IEC 61009-1 IEC 61009-2-2

Product details

The Schneider Electric A9D56806 is an Acti9 iC60 RCBO — a combined residual current breaker with overcurrent protection in a 1P+N, 18 mm wide modular package. It protects a single pole against overload and short-circuit (B curve, 3–5 x In magnetic trip) and adds integrated earth-leakage protection at 30 mA sensitivity, all in one DIN-rail module. Rated 6 A at 50 °C with a breaking capacity of 10 kA Icn at 240 V AC (IEC 61009-2-2), it's sized for final subcircuits in TN earthing systems — think lighting, socket outlets, or small appliance feeds where you need both overcurrent and earth-leakage protection in a single slot. The thermal-magnetic trip unit handles the overcurrent side; the integrated residual current module covers the 30 mA leakage. IP20 on the terminals, IP40 inside the modular enclosure — fine for dry indoor distribution boards.

Neutral on the left, phase on the right — standard Acti9 layout. Wire stripping length is 14 mm top, 13 mm bottom. Tightening torque: 3.5 N·m on the top screw clamp, 2 N·m on the bottom. The toggle gives local ON/OFF and fault indication — useful for quick visual checks on the panel door.

Rated for 5,000 electrical cycles and 20,000 mechanical cycles.

Frequently asked questions

Where can I buy A9D56806 and get pricing?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is the closest alternative to A9D56806 in the Acti9 family?

Within the Acti9 iC60 range, the main variant differences are rated current (In), curve (B/C/D), and earth-leakage sensitivity. The A9D56806 is a 6 A B-curve 30 mA unit; a higher-current or different-curve sibling would share the same footprint and terminal specs but change the protection characteristic.

What compliance documentation does this RCBO carry?

Certified to BS EN 61009-1, IEC 61009-1, and IEC 61009-2-2. The IP ratings are IP20 (terminals) and IP40 (modular enclosure) per IEC 60529.

MPN