Schneider Electric A9D57425
MPNA9D57425
Obsolete
A9D57425 - IC60N RCBO 4P 25A 30MA C 6000A AC by SQUARE D
$232.41Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | AC |
| Product or component type | Residual current breaker with overcurrent protection (RCBO) |
| Voltage | 500 V AC 50 Hz |
| [Ue] rated operational voltage | 380...415 V AC 50 Hz |
| [Uimp] rated impulse withstand voltage | 4 kV |
| Surge current | 250 A |
| Breaking capacity | 6000 A Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2 |
| Current | 25 A |
| Residual current tripping technology | Voltage independent |
| [Ics] rated service breaking capacity | 6000 A 100 % x Icn at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 6 kA 100 % x Icu at 380...415 V AC 50 Hz conforming to EN/IEC 60947-2 |
| Network frequency | 50 Hz |
All specifications
| Parameter | Value |
|---|---|
| Poles description | 4P |
| Number of protected poles | 4 |
| IP degree of protection | IP40 (distribution enclosure) conforming to IEC 60529 IP20 conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Connection pitch | 9 mm between poles |
| Wire stripping length | 12 mm for top or bottom connection |
| Connections - terminals | Tunnel type terminal top or bottom 1...35 mm² rigid Tunnel type terminal top or bottom 1...25 mm² flexible Tunnel type terminal top or bottom 1...25 mm² flexible with ferrule |
| Relative humidity | 95 % at 55 °C |
| Depth | 78 mm |
| Width | 72 mm |
| Color | White |
| Height | 86 mm |
| Electrical durability | 10000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947-2 EN/IEC 61009-2-1 |
| Range | Acti9 |
| Curve code | C |
| 9 mm pitches | 8 |
| Quality labels | KEMA-KEUR VDE IMQ NF |
| Tropicalisation | 2 |
| Limitation class | 1 conforming to EN/IEC 61009-2-1 |
| Local signalling | ON, OFF, fault trip |
| Device short name | iC60 RCBO |
| Tightening torque | 2 N.m |
| Device application | Distribution |
| Overvoltage category | III conforming to IEC 60364 |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 5...10 x In |
| Earth-leakage protection | Integrated |
| Device location in system | Outgoer |
| Earth-leakage sensitivity | 30 mA |
| Suitability for isolation | No conforming to IEC 60947-1 |
| Contact position indicator | No |
| Electromagnetic compatibility | 8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1 |
| Earth-leakage protection class | Type AC |
| Rated breaking and making capacity | Idm 6000 A at 380...415 V AC 50 Hz conforming to EN/IEC 61009-2-1 |
| Ambient air temperature for storage | -40...70 °C |
| Earth-leakage protection time delay | Instantaneous |
| Ambient air temperature for operation | -25...60 °C |
| Comb busbar and distribution block compatibility | Top or bottom: YES Bottom: biconnect |
MPN