It carries a 32 A rated current (In) on a C-curve magnetic trip (5–10× In) and integrated 30 mA earth-leakage protection, all in a single 36 mm wide module that clips onto a DIN rail. The 6 kA breaking capacity (Icn at 110–240 V AC, 50 Hz, per EN/IEC 61009-2-1) suits it for final-subcircuit protection in residential and light commercial distribution boards where the prospective fault current stays under that threshold.
Neutral is on the left, phase on the right. Terminals accept 1–16 mm² rigid or 1–10 mm² flexible at the top or bottom; tighten to 2 N·m with 15 mm strip length. IP20 finger-safe on the front face, IP40 inside a modular enclosure. Tropicalisation class 2 (IEC 60068-1) handles 95 % RH at 55 °C, so it's fine for coastal or unconditioned electrical rooms.